Hai, Tao and Ashraf Ali, Masood and Dhahad, Hayder A. and Alizadeh, As'ad and Sharma, Kamal and Fahad Almojil, Sattam and Ibrahim Almohana, Abdulaziz and Fahmi Alali, Abdulrhman and Attia, El-Awady (2023) A Novel Bi-Evaporator Cooling System via Integration of Absorption Refrigeration Cycle for Waste Energy Recovery from an Ejector-Expansion Trans-Critical CO2 (EETRCC) Cycle: Proposal and Optimization with Environmental Considerations. Sustainable Energy Technologies and Assessments, 57. p. 103118. ISSN 22131388
![[thumbnail of Research Article]](https://eprints.cihanuniversity.edu.iq/style/images/fileicons/text.png)
Article_SETA_14-03-2023.pdf - Published Version
Available under License Creative Commons Attribution Non-commercial No Derivatives.
Download (172kB)
Abstract
In this paper an integrated refrigeration system is designed, in which the waste heat from an ejector-expansion trans-critical CO2 (EETRCC) cooling scheme is used for the generation of cooling not only above but also below the temperature of zero degrees Celsius. Waste heat usage was accomplished via employment of an absorption refrigeration system in conjunction with a CO2 trans-critical refrigeration cycle. The absorption refrigeration cycle generates excess cooling above zero temperature utilizing the waste heat from ejector expansion system. Appropriate thermodynamic models are employed for feasibility assessment of integrated refrigeneration system, along with economic considerations to estimate produced cooling price. The results revealed significant better performance of novel integrated framework compared to standalone EETRCC cycle. In the best-case scenario, the levelized cost of cooling for the former is obtained as 105.3 $/GJ and, while the latter produces cooling with a levelized cost of 120.9 $/GJ. Also, it has been concluded that, when the temperature of the second evaporator is raised, the exergy efficiency of the system drops by 3 %, which results in increment of unit cost of the cooling by 6.34 %. In addition, highest exergy destructions are found to be 27.53 kW in the gas cooler and 15.57 kW in the generator.
Item Type: | Article |
---|---|
Uncontrolled Keywords: | Integrated, Refrigeration, System, Absorption, Ejector-Expansion |
Subjects: | T Technology > TD Environmental technology. Sanitary engineering |
Divisions: | Department of Civil Engineering > Research papers |
Depositing User: | ePrints Depositor |
Date Deposited: | 31 Oct 2024 11:31 |
Last Modified: | 31 Oct 2024 11:31 |
URI: | https://eprints.cihanuniversity.edu.iq/id/eprint/2534 |